Abstract :
Southwire Company is operating the world´s first high temperature superconducting (HTS) cable at its corporate headquarters in Carrollton, Georgia. The HTS system consists of three 30 m long single phase cables rated at 12.4 kV, 1250 A and is cooled by pressurized liquid nitrogen. The cable provides power to Southwire´s two main manufacturing plants and the machinery division. The cable was installed and energized on Jan. 6, 2000 for on-line testing and operation. The cables have provided 100% of the customer load for over 9500 hours, including over 2500 hours of unattended operation and is continuing. The HTS cable has proven reliable; it has not caused any power failure since its start up.
Keywords :
cooling; high-temperature superconductors; power cables; superconducting cables; 12.4 kV; 1250 A; 9500 h; Carrollton; Georgia; HTS cable; Southwire high temperature superconducting cable; customer load; high temperature superconducting cable; machinery division; manufacturing plants; on-line testing; power failure; pressurized liquid nitrogen cooling; single phase cables; unattended operation; Cable insulation; Cryogenics; Dielectrics; High temperature superconductors; Machinery; Manufacturing; Nitrogen; Power system reliability; Superconducting cables; Testing;