Title :
A Direct Calculation of Shift Factors Under Network Islanding
Author :
Yong Fu ; Zuyi Li
Author_Institution :
Electr. & Comput. Eng. Dept., Mississippi State Univ., Starkville, MS, USA
Volume :
30
Issue :
3
fYear :
2015
fDate :
May-15
Firstpage :
1550
Lastpage :
1551
Abstract :
The outage of transmission lines, especially of multiple lines, could cause power network islanding. Traditional line outage distribution factors cannot be directly used for the power flow calculation under network islanding. This letter proposes a direct and fast two-phase method for calculating shift factors under network islanding by leveraging existing shift factors of base case (pre-contingency) network.
Keywords :
power transmission lines; power transmission reliability; power network islanding; shift factors calculation; transmission line outage; two-phase method; Computers; Indexes; Islanding; Monitoring; Power transmission lines; Transmission line matrix methods; Contingency analysis; islanding; shift factor;