• DocumentCode
    3771707
  • Title

    Selection of insulating materials used in SF6 circuit breakers

  • Author

    K. H. Yoon

  • Author_Institution
    Westinghouse Electric Corporation Trafford, PA
  • fYear
    1977
  • Firstpage
    340
  • Lastpage
    345
  • Abstract
    This presents a method and the results of evaluations of insulating materials for SF6 circuit interruption to be built under a "Single Pressure SF6 Interrupter Research" project sponsored by the Electric Power Research Institute (EPRI). In view of the high interrupting and continuous current ratings involved, selected insulating materials were tested in 135°C and 500 psig arced SF6 gas environments. The finally selected materials showed no measurable leakage current during a 300 hour exposure test and they all withstood a surface voltage stress in excess of 85 kV/inch. These tests, therefore, demonstrated that SF6 is a viable insulating medium for even higher temperature and pressure, permitting higher performance and lower costs in future switchgear applications.
  • Keywords
    "Sulfur hexafluoride","Temperature measurement","Leakage currents","Current measurement","Dielectric measurement","Dielectric breakdown","Insulators"
  • Publisher
    ieee
  • Conference_Titel
    Electrical/Electronics Insulation Conference, 1977 EIC 13th
  • Print_ISBN
    978-1-5090-3112-2
  • Type

    conf

  • DOI
    10.1109/EIC.1977.7461977
  • Filename
    7461977