Abstract :
Tests were conducted to predict remaining electrical insulation life of a polyimide-epoxy insulated 60 kW form-wound homopolar inductor generator following completion of 23,130 hours of turbo-generator endurance tests. The generator stator was sectioned to provide five sections, designated statorettes, and to permit 33 coil dielectric measurements on each section. Thermal aging tests were conducted on each section at select elevated temperatures to establish an Arrhenius life-temperature plot for end-life prediction and product or application use.
Keywords :
"Rubber","Surface resistance","Gases","Surface discharges","Discharges (electric)"