DocumentCode :
3772530
Title :
Wide band measurements of partial discharge in epoxy
Author :
G.G. Stone;S.A. Boggs
Author_Institution :
Ontario Hydro Research Division, 800 Kipling Avenue, TORONTO, Canada, M8Z 5S4
fYear :
1982
fDate :
6/1/1982 12:00:00 AM
Firstpage :
137
Lastpage :
140
Abstract :
Continuous observation of partial discharge may enable warning of incipient failure of gas-insulated switchgear (GIS). This paper reports measurements of partial discharges from electric treeing in epoxy, as well as from artificial defects in a GIS test piece. The measurements were performed with an ultrawide detection bandwidth (up to 1 GHz). Some partial discharge pulses have durations of at most a few nanoseconds; a multichannel analyzer capable of responding to such fast pulses was developed for these experiments.
Keywords :
"Partial discharges","Shape","Needles","Partial discharge measurement","Gas insulation","Couplers","Conductors"