• DocumentCode
    3772530
  • Title

    Wide band measurements of partial discharge in epoxy

  • Author

    G.G. Stone;S.A. Boggs

  • Author_Institution
    Ontario Hydro Research Division, 800 Kipling Avenue, TORONTO, Canada, M8Z 5S4
  • fYear
    1982
  • fDate
    6/1/1982 12:00:00 AM
  • Firstpage
    137
  • Lastpage
    140
  • Abstract
    Continuous observation of partial discharge may enable warning of incipient failure of gas-insulated switchgear (GIS). This paper reports measurements of partial discharges from electric treeing in epoxy, as well as from artificial defects in a GIS test piece. The measurements were performed with an ultrawide detection bandwidth (up to 1 GHz). Some partial discharge pulses have durations of at most a few nanoseconds; a multichannel analyzer capable of responding to such fast pulses was developed for these experiments.
  • Keywords
    "Partial discharges","Shape","Needles","Partial discharge measurement","Gas insulation","Couplers","Conductors"
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1982 IEEE International Conference on
  • Print_ISBN
    978-1-5090-3123-8
  • Type

    conf

  • DOI
    10.1109/EIC.1982.7464452
  • Filename
    7464452