DocumentCode
3772530
Title
Wide band measurements of partial discharge in epoxy
Author
G.G. Stone;S.A. Boggs
Author_Institution
Ontario Hydro Research Division, 800 Kipling Avenue, TORONTO, Canada, M8Z 5S4
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
137
Lastpage
140
Abstract
Continuous observation of partial discharge may enable warning of incipient failure of gas-insulated switchgear (GIS). This paper reports measurements of partial discharges from electric treeing in epoxy, as well as from artificial defects in a GIS test piece. The measurements were performed with an ultrawide detection bandwidth (up to 1 GHz). Some partial discharge pulses have durations of at most a few nanoseconds; a multichannel analyzer capable of responding to such fast pulses was developed for these experiments.
Keywords
"Partial discharges","Shape","Needles","Partial discharge measurement","Gas insulation","Couplers","Conductors"
Publisher
ieee
Conference_Titel
Electrical Insulation, 1982 IEEE International Conference on
Print_ISBN
978-1-5090-3123-8
Type
conf
DOI
10.1109/EIC.1982.7464452
Filename
7464452
Link To Document