DocumentCode
3772539
Title
Evaluating the resistance of power cable insulation to ageing under thermal cycling and over-voltage conditions
Author
M?rcio A. Sens;John H. Mason
Author_Institution
CEPEL-Electrical Energy Research Centre, P.O. Box 2754, 20,000, Rio de Janeiro, Brazil
fYear
1982
fDate
6/1/1982 12:00:00 AM
Firstpage
171
Lastpage
174
Abstract
Equipment for automatic thermal cycling tests on power cables is described. Temperature measurements on an auxiliary cable carrying the same current, permit the temperature of the test cable to be controled and recorded while high voltage is applied. Preliminary tests on 15 and 25 kV cables with EP rubber insulation show that there was no deterioration after 20 cycles with the conductor at 90?C and at twice rated voltage (2 V0). The loss tangent of the 25 kV cable increased to about 50% over the initial value after 24 cycles at 130?C, but showed no further deterioration after 24 cycles at 150?C (at 3 V0). No significant discharges occurred in the cables after heat cycling.
Keywords
"Cable insulation","Oil filled cables","Power cables","Discharges (electric)","Aging","Temperature measurement"
Publisher
ieee
Conference_Titel
Electrical Insulation, 1982 IEEE International Conference on
Print_ISBN
978-1-5090-3123-8
Type
conf
DOI
10.1109/EIC.1982.7464461
Filename
7464461
Link To Document