• DocumentCode
    3772593
  • Title

    Detection of insulation deterioration through electrical spectrum analysis

  • Author

    James E. Timperley

  • Author_Institution
    American Electric Power Service Corporation, Canton, Ohio 44701
  • fYear
    1983
  • Firstpage
    60
  • Lastpage
    64
  • Abstract
    Several types of insulation deterioration common to large rotating electrical machines produce Electromagnetic Interference (EMI) at discrete frequencies or within bands of frequencies. This paper employs the use of standing wave calculations to predict these natural resonant points. Curves of measured impedance variation with frequency are presented to verify calculated values. Determination of these resonants is an important first step in real time monitoring and later physically locating a defect before failures occur.
  • Keywords
    "Resonant frequency","Stators","Conductors","Impedance","Frequency measurement","Insulation","Electromagnetic interference"