Title :
Failure anticipation in oil-paper insulation
Author_Institution :
Ontario Hydro, Research Division, 800 Kipling Avenue, Toronto, Canada M8Z 5S4
fDate :
6/1/1984 12:00:00 AM
Abstract :
Characteristics of partial discharges (pd) in oil-paper insulation models were studied. Such information is required as part of a larger project to develop apparatus to warn of an impending failure of oil-paper insulated high voltage transformers in normal service. Progressive growth of partial discharges from inception to failure of the insulation was monitored using a pulse height analyzer. The partial discharges have very large magnitudes (approximately 100 000 pC) during a period lasting from a few minutes to a few hours before the insulation fails. Hence it is feasible to give a warning of an incipient failure in oil-paper insulated station equipment using pd detection methods.
Keywords :
"Partial discharges","Insulation","Stress","Instrument transformers","Monitoring","Corona"
Conference_Titel :
Electrical Insulation, 1984 IEEE International Conference on
Print_ISBN :
978-1-5090-3124-5
DOI :
10.1109/EIC.1984.7465212