DocumentCode
3778809
Title
Online tan-δ measurement and investigation of insulation behavior during PD activity of PCCC in mercaptans contaminated transformer oil
Author
L. Sanjeev Kumar;B. Ramachandra;S. Senthil Kumar
Author_Institution
Electrical and Electronics Engg., Sri Siddhartha Institute of Technology, Tumakuru, Karnataka, India
fYear
2015
Firstpage
457
Lastpage
461
Abstract
Paper-oil insulation is widely used in transformers. It is reported that during life cycle of transformer, paper and pressboard insulation undergo deterioration because of increase in sulphur content in transformer oil. The reactive sulphur which forms copper sulfide and its deposition in paper-oil insulation system of in-service transformers results in degradation of insulation. The paper covered copper conductors (PCCC) in such oil medium leads to insulation failure. This paper presents tanδ behavior of insulation property of PCCC in transformer oil with reference to formation and migration of Mercaptans sulfur with online tanδ measurements.
Keywords
"Oil insulation","Power transformer insulation","Sulfur","Resistance","Partial discharges"
Publisher
ieee
Conference_Titel
Emerging Research in Electronics, Computer Science and Technology (ICERECT), 2015 International Conference on
Type
conf
DOI
10.1109/ERECT.2015.7499059
Filename
7499059
Link To Document