• DocumentCode
    3778809
  • Title

    Online tan-δ measurement and investigation of insulation behavior during PD activity of PCCC in mercaptans contaminated transformer oil

  • Author

    L. Sanjeev Kumar;B. Ramachandra;S. Senthil Kumar

  • Author_Institution
    Electrical and Electronics Engg., Sri Siddhartha Institute of Technology, Tumakuru, Karnataka, India
  • fYear
    2015
  • Firstpage
    457
  • Lastpage
    461
  • Abstract
    Paper-oil insulation is widely used in transformers. It is reported that during life cycle of transformer, paper and pressboard insulation undergo deterioration because of increase in sulphur content in transformer oil. The reactive sulphur which forms copper sulfide and its deposition in paper-oil insulation system of in-service transformers results in degradation of insulation. The paper covered copper conductors (PCCC) in such oil medium leads to insulation failure. This paper presents tanδ behavior of insulation property of PCCC in transformer oil with reference to formation and migration of Mercaptans sulfur with online tanδ measurements.
  • Keywords
    "Oil insulation","Power transformer insulation","Sulfur","Resistance","Partial discharges"
  • Publisher
    ieee
  • Conference_Titel
    Emerging Research in Electronics, Computer Science and Technology (ICERECT), 2015 International Conference on
  • Type

    conf

  • DOI
    10.1109/ERECT.2015.7499059
  • Filename
    7499059