DocumentCode
3780823
Title
The relation of capacitance increase with high voltages to internal electric discharges and discharging void volume
Author
Thomas W. Dakin
Author_Institution
Westinghouse Electric Corporation, Pittsburgh, Pennsylvania
fYear
1958
Firstpage
13
Lastpage
16
Abstract
Historically, power factor “tip up” or increase with voltage as a result of internal discharges has been a sort of qualitative indication of internal discharges and of an insulation quality. In European countries, the slope of the rising power factor voltage curve has been used in specifications of high voltage generator insulation. It is the purpose of this paper to emphasize the value of considering the capacitance increase associated with internal discharges at high voltages.
Keywords
"Capacitance","Discharges (electric)","Insulation","Mathematical model","Solids","Air gaps","Reactive power"
Publisher
ieee