DocumentCode :
3786447
Title :
Installation and commissioning of the helium refrigeration system for the CMS magnet
Author :
G. Perinic;T. Dupont;D. Legrand;M. Pezzetti
Author_Institution :
Eur. Organ. for Nucl. Res., Geneva, Switzerland
Volume :
14
Issue :
2
fYear :
2004
Firstpage :
1708
Lastpage :
1710
Abstract :
A new helium refrigeration plant with a cooling capacity of 800 W at 4.45 K, 4500 W between 60 K and 80 K, and 4 g/s liquefaction simultaneously has been installed in its temporary position inside the Compact Muon Solenoid assembly hall at CERN. The commissioning of the compressor station has been achieved, the commissioning of the cold box and the cryostats is under way. First operation results are presented.