• DocumentCode
    3786885
  • Title

    Influence of GIS parameters on the Topler constant

  • Author

    P. Osmokrovic;S. Krstic;M. Ljevak;D. Novakovic

  • Author_Institution
    Fac. of Electr. Eng., Belgade, Yugoslavia
  • Volume
    27
  • Issue
    2
  • fYear
    1992
  • Firstpage
    214
  • Lastpage
    220
  • Abstract
    An experimental study of formative times and the Topler´s constant approach to modeling the breakdown event is presented. The authors deal with the dependence of formative time and Topler´s constant on the macroscopic parameters of the insulation. Results obtained were statistically treated and the Topler´s constant dependence on the quoted parameters was determined. It was found that some insulator parameters (gas type, pressure, degree of inhomogeneity of electrical field) influenced the value of Topler´s constant, and that some other insulator parameters (electrode material, roughness of electrode surface) did not influence the value of Topler´s constant. The observed influence of insulator parameters on the value of Topler´s constant was not quantitatively significant. On the basis of the experimental results one can conclude that it is valid to apply Topler´s law in modeling the electrical breakdown for SF/sub 6/ and gas mixtures SF/sub 6//N/sub 2/, SF/sub 6//Ar under the tested conditions.
  • Keywords
    "Geographic Information Systems","Electric breakdown","Dielectrics and electrical insulation","Gas insulation","Electrodes","Nonuniform electric fields","Rough surfaces","Surface roughness","Surface treatment","Argon"
  • Journal_Title
    IEEE Transactions on Electrical Insulation
  • Publisher
    ieee
  • ISSN
    0018-9367
  • Type

    jour

  • DOI
    10.1109/14.135593
  • Filename
    135593