DocumentCode
3791584
Title
Probabilistic assessment of financial losses due to interruptions and voltage sags - part II: practical implementation
Author
J.V. Milanovic;C.P. Gupta
Author_Institution
Dept. of Electr. Eng., Indian Inst. of Technol. Roorkee, India
Volume
21
Issue
2
fYear
2006
Firstpage
925
Lastpage
932
Abstract
The second part of this paper presents a practical implementation and application of the methodology for the stochastic assessment of the annual financial losses due to interruptions and voltage sags discussed in the first part of this paper. The costs of interruptions and voltage sags are determined separately and then combined in order to estimate the total financial losses in the network. The methodology is illustrated on a generic realistic distribution network with all relevant network components modeled appropriately. Finally, different network topologies are compared taking into account total financial losses in the network. It is shown that the inclusion of the financial losses due to voltage sags that may account for up to about 20% of the interruption costs may alter the network topology ranking.
Keywords
"Voltage fluctuations","Power quality","Costs","Network topology","Consumer electronics","Investments","Bayesian methods","Power system reliability","Circuit breakers","Stochastic processes"
Journal_Title
IEEE Transactions on Power Delivery
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2006.870987
Filename
1610708
Link To Document