DocumentCode
3795811
Title
Harmonic domain analysis of field variables related to eddy current and hysteresis losses in saturated laminations
Author
N. Rajakovic;A. Semlyen
Author_Institution
Dept. of Electr. Eng., Toronto Univ., Ont., Canada
Volume
4
Issue
2
fYear
1989
Firstpage
1111
Lastpage
1116
Abstract
The authors give a detailed analysis of the space and time distribution of the field variables B, H, and E inside saturating laminations, using a harmonic domain modeling method. A simple way has been devised for the representation of hysteresis. It was found that hysteresis affects to a small degree the variation of H and B but has no noticeable influence on E and thus, as expected, does not interact with the corresponding eddy current losses. It is shown that saturation distorts the linear space distribution of the eddy currents but that the assumption of linear distribution still leads to a very simple method for eddy current loss calculation which is remarkably accurate at 60 Hz.
Keywords
"Harmonic analysis","Eddy currents","Hysteresis","Lamination","Iron","Steady-state","Computer simulation","Computational modeling","Transformer cores","Maxwell equations"
Journal_Title
IEEE Transactions on Power Delivery
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.25593
Filename
25593