Abstract
Summary form only given, as follows. Diagnostic measurements performed for surge arresters are normally studied by evaluating their suitability to detect ageing and degradation of metal oxide material. The suitability of different methods for revealing internal moisture in arresters has not been studied much. This aspect is considered in the paper based on measurement results obtained during a 1.5 year laboratory test series conducted for six different types of polymer housed distribution class arresters. AC power losses, third harmonic content of resistive leakage current, DC leakage current and partial discharge measurement results over the test period are given and discussed. Details of the measurement procedures suitable for measuring polymeric arresters with internal moisture are also studied. AC power loss and DC leakage current measurements were found to be good methods, while the other two can only be used as additional methods when diagnosing Internal moisture In polymer housed arresters.
Keywords
ageing; arresters; electric current measurement; insulation testing; leak detection; leakage currents; loss measurement; partial discharge measurement; polymers; AC power losses; DC leakage current; ageing; degradation; internal moisture diagnostic methods; partial discharge measurement; polymer-housed metal oxide surge arresters; resistive leakage current; third harmonic content; Aging; Arresters; Degradation; Leakage current; Moisture measurement; Partial discharge measurement; Performance evaluation; Polymers; Surges; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Summer Meeting, 2002 IEEE
Conference_Location
Chicago, IL, USA
Print_ISBN
0-7803-7518-1
Type
conf
DOI
10.1109/PESS.2002.1043252
Filename
1043252
Link To Document