DocumentCode :
383007
Title :
Evaluation of line surge arrester failure rate using multipulse lightning stresses
Author :
Zanetta, L.C., Jr.
Author_Institution :
Sao Paulo Univ., Brazil
Volume :
1
fYear :
2002
fDate :
25-25 July 2002
Abstract :
Summary form only given, as follows. This paper develops a method to analyze energy stresses on transmission line surge arresters. The approach computes the failure rate of arresters due to energy stresses, convolving the density probabilities of first and subsequent pulses. Multipulse stroke effects are considered in a 138 kV line case study, typical of single circuit lines, located in regions with high densities of ground flashes, in SE Brazil. The proposed method provides an improved insight into energy stress evaluation for selection of line surge arresters.
Keywords :
arresters; power transmission faults; power transmission lines; power transmission protection; probability; 138 kV; Brazil; density probabilities; energy stresses; line surge arrester failure rate; multipulse lightning stresses; multipulse stroke effects; transmission line surge arresters; Arresters; Insulation; Lightning; Stress; Surges; Transmission lines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Engineering Society Summer Meeting, 2002 IEEE
Conference_Location :
Chicago, IL, USA
Print_ISBN :
0-7803-7518-1
Type :
conf
DOI :
10.1109/PESS.2002.1043254
Filename :
1043254
Link To Document :