Title :
Application of steady-state harmonic distortion limits to the time-varying measured harmonic distortions
Author_Institution :
Dept. of Electr. & Comput. Eng., Alberta Univ., Edmonton, Alta., Canada
Abstract :
Harmonic distortion limits recommended by the majority of known standards are for steady-state harmonics. The harmonic distortions measured in the field, however, vary with time. How to apply the steady-state limits to the actual measured harmonics has been a concern for verifying compliance to harmonic standards. In this panel paper, the problem of time-varying harmonics is examined and a solution is proposed. The proposed solution is to convert the time-varying distortion data into two magnitude-duration curves. The steady-state limits are then modified and applied to the magnitude-duration curves.
Keywords :
harmonic distortion; power system harmonics; standards; harmonic standards compliance; magnitude-du ration curves; steady-state harmonic distortion limits; time-varying distortion data; time-varying measured harmonic distortions; Application software; Distortion measurement; Fourier transforms; Frequency conversion; Harmonic distortion; Measurement standards; Sampling methods; Steady-state; Time measurement; Voltage;
Conference_Titel :
Power Engineering Society Summer Meeting, 2002 IEEE
Conference_Location :
Chicago, IL, USA
Print_ISBN :
0-7803-7518-1
DOI :
10.1109/PESS.2002.1043510