Title
Application of AC equivalent to total transfer capability evaluation using two-step method
Author
Audomvongseree, K. ; Yokoyama, A.
Author_Institution
Dept. of Electr. Eng., Univ. of Tokyo, Japan
Volume
1
fYear
2002
fDate
13-17 Oct 2002
Firstpage
383
Abstract
This paper proposes a method for calculating TTC including many security limits. This method is based on two-step process. First, with linear estimation method, the active constraint that limits the power transfer is predicted. Then, after the active constraint is known, the augmented Newton-Raphson load flow is calculated to evaluate the accurate TTC. In addition, due to the network size problem, AC equivalent model is used in this paper. The TTC obtained from IEEE 118 buses and 300 buses systems with this method show that this proposed method provides satisfactory results with short computation time.
Keywords
Newton-Raphson method; electricity supply industry deregulation; load flow; power transmission; IEEE 118 bus systems; IEEE 300 bus systems; active constraint; augmented Newton-Raphson load flow; linear estimation method; network partitioning; power system deregulation; security limits; total transfer capability; two-step method; Admittance; Computer networks; Equations; Load flow; Power system analysis computing; Power system modeling; Power system security; Power systems; Transmission line measurements;