Reliability assurance of HVDC thyristor valves by rigorous type tests
Author
Sheng, Baoliang ; Rudervall, Roberto ; Bjarme, Hans-Ola ; Saksvik, Olaf
Author_Institution
Power Syst., ABB Utilities AB, Ludvika, Sweden
Volume
1
fYear
2002
fDate
13-17 Oct 2002
Firstpage
500
Abstract
Rigorous type tests are essential to ensure the reliability of HVDC thyristor valves. A conventional six-pulse back-to-back direct test circuit is a proper representative of an actual network to test the valves. The test equivalence by this circuit has been proven by the reliable operations of valves installed worldwide. To keep pace with the fast development of power handling capability per single thyristor, an alternative test circuit, synthetic test circuit has been developed to continuously hold the stringent type test program of ABB s HVDC thyristor valves. With properly defined test parameters, both the conventional six-pulse back-to-back direct test circuit and the synthetic test circuit can produce the stresses equal to or greater than the worst-case service stresses. As a result, higher reliability is exhibited by the tested valves.
Keywords
HVDC power convertors; circuit reliability; semiconductor device measurement; semiconductor device testing; testing; thyristor convertors; HVDC thyristor valves reliability assurance; power handling capability; rigorous type tests; six-pulse back-to-back direct test circuit; test parameters; Circuit testing; Dielectrics; Fault currents; HVDC transmission; Heart valves; IEC standards; Laboratories; Stress; Thyristors; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on
Print_ISBN
0-7803-7459-2
Type
conf
DOI
10.1109/ICPST.2002.1053593
Filename
1053593
Link To Document