• DocumentCode
    3851815
  • Title

    Analysis of accelerated ageing of non-ceramic insulation equipments

  • Author

    R. Hernandez;I. Ramirez;R. Saldivar;G. Montoya

  • Author_Institution
    Instituto De Investigaciones Electricas, Reforma 113 Cuernavaca, Morelos, Mexico
  • Volume
    6
  • Issue
    1
  • fYear
    2012
  • fDate
    1/1/2012 12:00:00 AM
  • Firstpage
    59
  • Lastpage
    68
  • Abstract
    Ageing of non-ceramic insulation can conduct into failures of the power system, where usually pollution plays an important role in the degradation process. These failures cannot be evaluated by applying IEC 61109 ageing tests, because such tests are considered as screening tests and up to now these tests are quite questionable. Therefore research of new test methods and diagnostic tools are needed to predict long-term performance of non-ceramic insulators. A non-standard method for insulation ageing is modified and used in this work to evaluate non-ceramic components of breakers, bushings and surge arresters. Different diagnostic tests are proposed to analyse the evolution in the degradation process of these apparatus. The results showed that the applied methodology and the proposed tests may evaluate in a more realistic way the performance of new non-ceramic insulating material used in electrical equipment.
  • Journal_Title
    IET Generation, Transmission & Distribution
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2011.0078
  • Filename
    6128770