• DocumentCode
    3861727
  • Title

    Efficient reduction of fault current through the grounding grid of substation supplied by cable line

  • Author

    L.M. Popovic

  • Author_Institution
    J.P. Elektrodistribucija Beograd, Yugoslavia
  • Volume
    15
  • Issue
    2
  • fYear
    2000
  • Firstpage
    556
  • Lastpage
    561
  • Abstract
    The paper presents an analytical procedure suitable for the determination of the part of the ground fault current emanating from the substation grounding grid in the conditions when a particular measure has been taken to reduce it. The practical realization of this measure can be simply described as burying one bare copper wire of a certain length in the same trench as the cable feeding line. In the case of an overhead feeding line, the similar measure is denoted in the expert literature as the "counterpoise". The presented method enables a quick and, for practical purposes, sufficiently accurate evaluation of the copper wire length providing the maximum possible reduction of the substation grid current. The conveniences of the method result from the simplicity of the formulae for the determination of the realized grid current reduction at the effective copper wire length.
  • Keywords
    "Fault currents","Grounding","Substations","Power cables","Wire","Copper","Voltage","Oil filled cables","Current measurement","Safety"
  • Journal_Title
    IEEE Transactions on Power Delivery
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.852984
  • Filename
    852984