DocumentCode
3861942
Title
The impact of the induction motor on short-circuit current
Author
Z. Maljkovic;M. Cettolo;M. Pavlica
Author_Institution
Zagreb Univ., Croatia
Volume
7
Issue
4
fYear
2001
Firstpage
11
Lastpage
17
Abstract
Simplified analytical models for calculation of the induction motor´s short-circuit current are presented. Laboratory tests have been performed on two induction motors with low power rating, 26 kW and 122 kW, respectively, in order to measure their short-circuit current. Results calculated according to the available literature have been compared to those acquired by testing. Calculations have also been made for a high-voltage induction motor rated 1250 kW, whose parameters have been known.
Keywords
"Induction motors","Protective relaying","Circuit testing","Laboratories","Voltage","Circuit faults","Synchronous motors","Induction generators","Synchronous machines","Synchronous generators"
Journal_Title
IEEE Industry Applications Magazine
Publisher
ieee
ISSN
1077-2618
Type
jour
DOI
10.1109/2943.930986
Filename
930986
Link To Document