DocumentCode :
3863448
Title :
Interpretation of power factor values throughout the life of cast epoxy condenser bushings
Author :
F. S. Brugner
Author_Institution :
Square D Company, Clearwater, Florida, United States
fYear :
1984
fDate :
6/1/1984 12:00:00 AM
Firstpage :
252
Lastpage :
257
Abstract :
The power factor and partial discharge values for cast cycloaliphatic epoxy condenser bushings that have been aged in a humidity chamber at 40°C, 90 percent relative humidity are given. A prediction for the long term saturation value of the power factor and when it will occur in service is given for bushings manufactured with and without silane surfactants. Recommendations are made for acceptable annual increase in power factor for bushings in service. The use of power factor measurement as a field technique for the evaluation of cast cycloaliphatic epoxy condenser bushing integrity is discussed.
Keywords :
"Reactive power","Insulators","Humidity","Moisture","Power measurement","Aging"
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1984 IEEE International Conference on
Print_ISBN :
978-1-5090-3124-5
Type :
conf
DOI :
10.1109/EIC.1984.7465191
Filename :
7465191
Link To Document :
بازگشت