Title :
First application of composite insulator termination for XLPE cable in Japan
Author :
Toya, Atsushi ; Aihara, Yasuhiko ; Iizuka, Hiroyuki ; Yonemura, Tokui
Author_Institution :
Tokyo Electr. Power Co. Inc., Japan
Abstract :
Composite insulators have a number of advantages over porcelain insulators, including lighter weight, better contamination performance and explosion resistance, and easier construction. They are therefore being considered for use with outdoor terminations for XLPE cable especially for those installed on pylon branching. Tokyo Electric and Furukawa Electric have jointly developed 66 kV and 154 kV outdoor terminations with composite insulators. This article presents the primary advantages of the composite insulator and the electrical performance of the termination for XLPE cable using composite insulator instead of a porcelain one. Also, the specification of the 66 kV and 154 kV composite insulator terminations applied to the Tokyo Electric Power´s Oihama Line and Koai Line are introduced.
Keywords :
XLPE insulation; composite insulators; electric connectors; power cable insulation; 154 kV; 66 kV; Furukawa Electric; Japan; Koai Line; Oihama Line; Tokyo Electric; XLPE cable; composite insulator termination; contamination performance; explosion resistance; outdoor terminations; porcelain insulators; pylon branching; Cable insulation; Contamination; Dielectrics and electrical insulation; Plastic insulation; Poles and towers; Porcelain; Rubber; Safety; Testing; Workability;
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
DOI :
10.1109/TDC.2002.1177626