DocumentCode :
389858
Title :
Investigation of hot gas flow in a dead-tank-type gas circuit breaker
Author :
Uchii, T. ; Kawano, H. ; Nishiwaki, S.
Author_Institution :
Toshiba Corp., Kawasaki, Japan
Volume :
2
fYear :
2002
fDate :
6-10 Oct. 2002
Firstpage :
1461
Abstract :
This paper describes the behavior of hot gas flow during a large current interruption, which may cause a ground fault in a dead-tank-type gas circuit breaker even if hot gas is locally distributed between live part and grounded tank. By observations with high-speed-video and measurements of breakdown voltage with small gaps it became clear that gas temperature and electrical field strength at the mouth of exhaust tube are decisive to ground fault occurrence. How to avoid a ground fault and to efficiently select the optimal dimensions of an exhaust tube for a compact and reliable dead-tank-type GCB is shown.
Keywords :
SF6 insulation; electric breakdown; electrical faults; gas blast circuit breakers; high-speed optical techniques; voltage measurement; SF6; SF6 circuit breaker; breakdown voltage measurement; electrical field strength; exhaust tube mouth; gas circuit breaker; gas temperature; ground fault; ground fault occurrence; grounded tank; high speed video; hot gas flow; large current interruption; live part; optimal dimensions; Circuit breakers; Circuit faults; Dielectrics; Electric breakdown; Fluid flow; Land surface temperature; Plasma temperature; Postal services; Sulfur hexafluoride; Transient analysis;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
Type :
conf
DOI :
10.1109/TDC.2002.1177696
Filename :
1177696
Link To Document :
بازگشت