• DocumentCode
    389871
  • Title

    AES Sul´s experiences using series compensation on medium-voltage distribution system

  • Author

    De Oliveira, H. R P M ; Papaleo, G.K. ; Figueiredo, C.E.C. ; de Jesus, N.C. ; Martinez, M.L.B.

  • Volume
    3
  • fYear
    2002
  • fDate
    6-10 Oct. 2002
  • Firstpage
    2061
  • Abstract
    This work relates the experience of AES Sul on implementing series compensation to solve voltage drop problems on feeders. First, measures from a system, which present about 300% of compensation, will be showed. During the energizing, that feeder presented significant voltage oscillation. It occurred on every test was made due to the coupled between series capacitor and three-phase induction motors used in pumps on rice farms. The analyze of that situation showed significant voltage instability what makes impossible its work. After the analyze of damp insertion on electromagnetic transient programs, it was decided to install this series capacitor in another feeder. On that other feeder, the results were good, obtaining an elevated compensation level and a well voltage behavior. These results are also presented on this work.
  • Keywords
    compensation; damping; induction motors; power capacitors; power distribution control; power supply quality; power system transients; reactive power control; Brazil; damp insertion; electromagnetic transient programs; feeder voltage drop; medium-voltage distribution system; pumps; rice farms; series capacitor; series compensation; three-phase induction motors; Capacitors; Couplings; Electromagnetic analysis; Induction motors; Medium voltage; Power quality; Regulators; Steady-state; Testing; Voltage control;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
  • Print_ISBN
    0-7803-7525-4
  • Type

    conf

  • DOI
    10.1109/TDC.2002.1177778
  • Filename
    1177778