DocumentCode :
389908
Title :
Development of self-extinguishing SF6 interrupter in medium voltage class
Author :
Lee, B.W. ; Sohn, J.M. ; Kim, D.K. ; Kim, Y.K.
Author_Institution :
R&D Res. Center, LG Ind. Syst., Chung Buk, South Korea
Volume :
1
fYear :
2002
fDate :
6-10 Oct. 2002
Firstpage :
430
Abstract :
This paper considers the research and development of the new type hybrid interrupter, which adopts both rotating arc and thermal expansion technology. The operating principle of this device depends on rapid arc rotation due to the magnetic field created by the fault current through a coil, which is mounted on contacts and also relies on the principle of thermal expansion created by arc energy in extinguishing chamber and finally causes pressure rise in expansion volume. To develop this type of interrupter, arc generation facility was constructed and to visualize arc movement in this chamber, highspeed camera measurement was introduced. In this research, the principles of the interrupting techniques are given and some experimental results of hybrid interrupter, which is developed by new technology, is introduced.
Keywords :
SF6 insulation; circuit-breaking arcs; fault currents; interrupters; magnetic fields; MV self-extinguishing SF6 interrupter; SF6; arc extinction; extinguishing chamber; hybrid interrupter; magnetic field; operating principle; research and development; rotating arc; thermal expansion technology; Cameras; Circuit breakers; Fault currents; Interrupters; Medium voltage; Paper technology; Research and development; Sulfur hexafluoride; Switchgear; Thermal expansion;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES
Print_ISBN :
0-7803-7525-4
Type :
conf
DOI :
10.1109/TDC.2002.1178400
Filename :
1178400