Title :
Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants—Part I: Problem Statement
Author :
Hooshyar, Ali ; Azzouz, Maher A. ; El-Saadany, Ehab F.
Author_Institution :
Electr. & Comput. Eng., Univ. of Waterloo, Waterloo, ON, Canada
Abstract :
The fault ride-through (FRT) requirement of modern grid codes results in interactions between full-scale converter-interfaced renewable energy power plants (CIREPPs) and the protection systems of high-voltage transmission grids, which normally involve distance elements either as the primary or the backup relay. Such interactions are influenced by the CIREPPs´ exclusive fault behavior, and have been left largely unnoticed in relaying literature. Part I of this paper develops a CIREPP model suitable for relaying studies, and highlights the CIREPP properties by which the protection system is endangered the most. Then, the operating scenarios leading to the malfunction of a distance relay that is located at a CIREPP substation and protects the adjacent line are unveiled. These scenarios include in-zone short circuits missed by the relay and incorrect tripping for out-of-zone faults, which would, in turn, neutralize FRT schemes implemented inside CIREPPs. The findings of this study also hold true for the ac lines emanating from voltage-sourced converter-based HVDC connections.
Keywords :
HVDC power convertors; HVDC power transmission; high-voltage techniques; power generation faults; power generation protection; power generation reliability; power grids; power transmission lines; relay protection; renewable energy sources; short-circuit currents; substation protection; AC line emanation; CIREPP model; CIREPP substation; adjacent line protection; backup relay; converter-interfaced renewable energy power plant; distance protection; distance relay; fault ride through capability; grid codes; high-voltage transmission grids; in-zone short circuits; neutralize FRT scheme; out-of-zone faults; protection systems; tripping; voltage sourced converter-based HVDC connection; Circuit faults; Fault currents; Impedance; Reactive power; Relays; Resistance; Converter-interfaced renewable energy power plant (CIREPP); line distance relay; photovoltaic farm; type IV wind farm;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2014.2369479