• DocumentCode
    391728
  • Title

    Experimental investigation of distribution transformer aged solid insulation

  • Author

    Mousavi, M.J. ; Butler-Purry, K.L.

  • Author_Institution
    Dept. of Electr. Eng., Texas A&M Univ., College Station, TX, USA
  • Volume
    2
  • fYear
    2002
  • fDate
    4-7 Aug. 2002
  • Abstract
    In this paper, a laboratory test setup designed to perform transformer insulation experiments at low voltage level is introduced. Monitoring the leakage current flowing through the insulation samples that are taken from an aged distribution transformer is the principle of the investigation. The electrode system utilized and the experimental procedure are described. The test results that highlight important aspects of the insulation behavior concerning incipient fault detection and diagnosis is addressed. The results help identify particular phenomena that might happen when an incipient fault initiates and taking them into account in the characterization of such faults to develop a detection method for the distribution transformer incipient fault.
  • Keywords
    ageing; electrodes; insulation testing; leakage currents; power transformer insulation; power transformer testing; detection method; distribution transformer aged solid insulation; electrode system; fault detection; fault diagnosis; incipient fault; laboratory test setup; leakage current monitoring; low voltage level; transformer insulation experiments; Aging; Fault detection; Fault diagnosis; Insulation testing; Laboratories; Low voltage; Monitoring; Performance evaluation; Power transformer insulation; Solids;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Circuits and Systems, 2002. MWSCAS-2002. The 2002 45th Midwest Symposium on
  • Print_ISBN
    0-7803-7523-8
  • Type

    conf

  • DOI
    10.1109/MWSCAS.2002.1186830
  • Filename
    1186830