DocumentCode
398886
Title
Optimized design of multiple-supply service trench
Author
Schlabbach, Jürgen
Author_Institution
Univ. of Appl. Sci., Bielefeld, Germany
Volume
1
fYear
2003
fDate
22-24 Sept. 2003
Firstpage
95
Abstract
Two different standardized trench layouts, containing, gas and water pipelines, telephone cables, 1-kV and 10kV-cables (LV and MV-cables), so-called multiple-supply service trenches, were analyzed with respect to their thermal loading. In principle, two different options were regarded, i.e. with currents in the cables according to VDE 0276 part 1000 and based on the current obtained for the maximal permissible temperature of the cable conductor as determined by the calculating program. The calculations according standard loading conditions resulted for realistic thermal soil conditions (λ = 1.5Km/W; ϑsoil = 15 C) in a maximal temperature of the water pipe of 20.1 C assuming a water temperature of 18 C. In case of the worst conditions i.e. λ = 1.5Km/W; ϑsoil = 15 C the maximal temperature for the water pipe will increase up to 21.5 C.
Keywords
CAD; cable laying; design engineering; pipelines; LV cable; MV cable; cable conductor; cable loading; cable trench; gas pipeline; maximal permissible temperature; multiple-supply service trench; permissible current; thermal loading; thermal soil condition; water pipeline; Conductors; Design optimization; Pipelines; Power cables; Protection; Soil; Telephony; Temperature; Thermal loading; Water heating;
fLanguage
English
Publisher
ieee
Conference_Titel
EUROCON 2003. Computer as a Tool. The IEEE Region 8
Print_ISBN
0-7803-7763-X
Type
conf
DOI
10.1109/EURCON.2003.1247986
Filename
1247986
Link To Document