• DocumentCode
    419953
  • Title

    A new scheme for power transformer protection

  • Author

    Yang, J.C. ; Yin, X.G. ; Chen, D.S. ; Zhang, Z. ; Wang, Z.H.

  • Author_Institution
    Dept. of Electr. Eng., Huazhong Univ. of Sci. & Technol., Wuhan, China
  • Volume
    1
  • fYear
    2003
  • fDate
    7-12 Sept. 2003
  • Firstpage
    354
  • Abstract
    In this paper, a new transformer protection scheme is proposed which is based on the combination of virtual 3rd harmonic restrained and sampled value differential principles. The differential protection restrained by virtual 3rd harmonic can identify asymmetric and symmetric inrush currents with semi-cycle data window and accelerate the protection tripping speed. The sampled value differential protection can overcome some disadvantages of harmonic restraining with a long delay in the case of high content of harmonic components during internal faults. The combination scheme takes advantages of these two methods and improves the protection performance effectively. Test results in Electrical Power Dynamic Laboratory (EPDL) illustrate the proposed scheme. Now the protection system has been put into trial operation in GeZouBa Hydroelectric Power Plant.
  • Keywords
    fault currents; power engineering computing; power system protection; power transformer protection; Electrical Power Dynamic Laboratory; GeZouBa Hydroelectric Power Plant; differential protection; inrush currents; internal faults; power transformer protection; protection tripping speed; semicycle data window; virtual 3rd harmonic differential principles; Circuit faults; Delay; Fault currents; Laboratories; Power system dynamics; Power system harmonics; Power system protection; Power transformers; Surge protection; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Transmission and Distribution Conference and Exposition, 2003 IEEE PES
  • Print_ISBN
    0-7803-8110-6
  • Type

    conf

  • DOI
    10.1109/TDC.2003.1335247
  • Filename
    1335247