DocumentCode
422859
Title
Detecting and close-loop control methods for selective-harmonic-compensation active power filter
Author
Hao, Wang ; Chao, Zhang ; Geng, Yang ; Ji-Hong, Du
Author_Institution
Dept. of Autom., Tsinghua Univ., Beijing
Volume
1
fYear
2004
fDate
14-16 Aug. 2004
Firstpage
206
Abstract
This paper presents a selective harmonic detecting method and a new close-loop control algorithm for selective-harmonic-compensation active power filters (SHC-APF). The SHC-APF consists of a selective detection unit, DC voltage control and current control loops. Selective harmonic detection unit detects precisely the selected harmonic currents instead of all harmonics produced by distorting loads. At the same time, the unit adds a preceding compensatory angle in order to compensate the infection of delays caused by the digital controller and voltage-source inverter (VSI). The algorithms for the closed-loop control are discussed. Simulations for the harmonic detection and control loop response are implemented and the results confirm the theoretical analysis
Keywords
active filters; delays; digital control; electric current control; harmonic distortion; invertors; power conversion harmonics; power harmonic filters; voltage control; DC voltage control; VSI; active power filter; close-loop control algorithm; control loop response; current control; delay compensation; digital controller; harmonic detecting method; load distortion; selective-harmonic-compensation; voltage-source inverter;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Motion Control Conference, 2004. IPEMC 2004. The 4th International
Conference_Location
Xi´an
Print_ISBN
7-5605-1869-9
Type
conf
Filename
1377813