DocumentCode
433841
Title
Magnetic field immunity of the low voltage current breakers installed inside the ITER tokamak building
Author
De Lorenzi, A. ; Bettanini, G. ; Desideri, D. ; Grando, L.
Author_Institution
Consorzio RFX, Assoc. EURATOM-ENEA, Padova, Italy
fYear
2003
fDate
14-17 Oct. 2003
Firstpage
610
Lastpage
613
Abstract
Two typologies of circuit breakers for low voltage distribution system have been extensively tested immersed in a static magnetic field, an environmental condition similar to what is expected inside the ITER tokamak building. Functionality tests with and without load, protection relay tests and life tests at nominal ratings have been performed. The results allowed to point out a magnetic field limit for regular operation irrespective of the installation, to find the operability limits for higher magnetic field and to assess if magnetic field changes the wearing during the life.
Keywords
Tokamak devices; circuit breakers; plasma toroidal confinement; ITER tokamak building; circuit breakers; functionality tests; life tests; low voltage current breakers; low voltage distribution system; magnetic field immunity; magnetic field limit; nominal ratings; protection relay tests; static magnetic field; Circuit breakers; Circuit testing; Life testing; Low voltage; Magnetic fields; Performance evaluation; Protection; Protective relaying; System testing; Tokamaks;
fLanguage
English
Publisher
ieee
Conference_Titel
Fusion Engineering, 2003. 20th IEEE/NPSS Symposium on
Print_ISBN
0-7803-7908-X
Type
conf
DOI
10.1109/FUSION.2003.1426721
Filename
1426721
Link To Document