DocumentCode
435389
Title
Influence of the supply of reactive power in the calculation of the transfer capability
Author
Gaino, F.C. ; Padilha-Feltrin, A.
Author_Institution
Dept. of Electr. Eng., Univ. Estadual Paulista, Sao Paulo, Brazil
fYear
2004
fDate
8-11 Nov. 2004
Firstpage
190
Lastpage
195
Abstract
This paper presents some initial concepts for including reactive power in linear methods for computing available transfer capability (ATC). It is proposed an approximation for the reactive power flows computation that uses the exact circle equations for the transmission line complex flow, and then it is determined the ATC using active power distribution factors. The transfer capability can be increased using the sensitivities of flow that show the best group of buses which can have their reactive power injection modified in order to remove the overload in the transmission lines. The results of the ATC computation and of the use of the sensitivities of flow are presented using the Cigre 32-bus system.
Keywords
power system analysis computing; power transmission lines; reactive power; transmission network calculations; Cigre 32-bus system; active power distribution factors; available transfer capability; flow sensitivities; linear methods; maximum capability transfer; reactive power flows; reactive power injection modified; reactive power supply; transmission line complex flow; Distributed computing; Equations; Power distribution; Power generation; Power supplies; Power system planning; Power transmission lines; Reactive power; Safety; Sensitivity analysis;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition: Latin America, 2004 IEEE/PES
Print_ISBN
0-7803-8775-9
Type
conf
DOI
10.1109/TDC.2004.1432375
Filename
1432375
Link To Document