DocumentCode
45724
Title
Low computational burden grid voltage estimation for grid connected voltage source converter-based power applications
Author
Gholami-Khesht, Hosein ; Monfared, Mohammad ; Golestan, Saeed
Author_Institution
Dept. of Electr. Eng., Ferdowsi Univ. of Mashhad, Mashhad, Iran
Volume
8
Issue
5
fYear
2015
fDate
5 2015
Firstpage
656
Lastpage
664
Abstract
This study presents a simple and efficient approach for grid voltage estimation based on the converter equations in the stationary reference frame. The proposed technique is adopted for the sensorless operation of the voltage source converter-based power conditioners. In this study, the effectiveness of the proposed estimation method when it is combined with a proportional-resonant (PR)-based current controller is investigated. When the PR controller is combined with the proposed voltage estimation technique, it offers an additional benefit, such that the grid voltage synchronisation is done without using any phase-locked loop or band-pass filter. The proposed sensorless control method shows an excellent steady-state and transient performance. It is proven through extensive simulations and experiments that the grid voltage estimation with a very low computational burden is achieved even when the grid voltage is distorted.
Keywords
electric current control; power convertors; sensorless machine control; synchronisation; converter equations; grid connected voltage source converter based power applications; grid voltage synchronisation; low computational burden grid voltage estimation; proportional resonant based current controller; sensorless control method; sensorless operation; stationary reference frame; voltage estimation technique;
fLanguage
English
Journal_Title
Power Electronics, IET
Publisher
iet
ISSN
1755-4535
Type
jour
DOI
10.1049/iet-pel.2014.0466
Filename
7095718