• DocumentCode
    45724
  • Title

    Low computational burden grid voltage estimation for grid connected voltage source converter-based power applications

  • Author

    Gholami-Khesht, Hosein ; Monfared, Mohammad ; Golestan, Saeed

  • Author_Institution
    Dept. of Electr. Eng., Ferdowsi Univ. of Mashhad, Mashhad, Iran
  • Volume
    8
  • Issue
    5
  • fYear
    2015
  • fDate
    5 2015
  • Firstpage
    656
  • Lastpage
    664
  • Abstract
    This study presents a simple and efficient approach for grid voltage estimation based on the converter equations in the stationary reference frame. The proposed technique is adopted for the sensorless operation of the voltage source converter-based power conditioners. In this study, the effectiveness of the proposed estimation method when it is combined with a proportional-resonant (PR)-based current controller is investigated. When the PR controller is combined with the proposed voltage estimation technique, it offers an additional benefit, such that the grid voltage synchronisation is done without using any phase-locked loop or band-pass filter. The proposed sensorless control method shows an excellent steady-state and transient performance. It is proven through extensive simulations and experiments that the grid voltage estimation with a very low computational burden is achieved even when the grid voltage is distorted.
  • Keywords
    electric current control; power convertors; sensorless machine control; synchronisation; converter equations; grid connected voltage source converter based power applications; grid voltage synchronisation; low computational burden grid voltage estimation; proportional resonant based current controller; sensorless control method; sensorless operation; stationary reference frame; voltage estimation technique;
  • fLanguage
    English
  • Journal_Title
    Power Electronics, IET
  • Publisher
    iet
  • ISSN
    1755-4535
  • Type

    jour

  • DOI
    10.1049/iet-pel.2014.0466
  • Filename
    7095718