• DocumentCode
    461295
  • Title

    Measurement of the Switching Over-Voltages at the Disconnection of the High Voltage Shunt Reactors in the Romanian Power System

  • Author

    Stroica, P.C. ; Merfu, I. ; Merfu, M.

  • Author_Institution
    SMART S.A., Craiova
  • Volume
    3
  • fYear
    2006
  • fDate
    9-13 July 2006
  • Firstpage
    1812
  • Lastpage
    1817
  • Abstract
    The paper presents the measurements of the switching over-voltages made in the Romanian Power System, at the 400/220/110 kV Urechesti substation at the disconnection of a 400 kV, 100 MVAr shunt reactor type DFAL, Siemens, Germany, in 3 consecutive versions. The first one is for shunt reactor controlled by live-tank oil circuit breaker, the second one is for shunt reactor controlled by SF6 circuit breaker, and the third one is for shunt reactor controlled by SF6 circuit breaker and synchronize device.
  • Keywords
    gas insulated switchgear; oil circuit breakers; overvoltage; power system measurement; reactors (electric); switching substations; voltage measurement; DFAL; Romanian Power System; SF6 circuit breaker; Urechesti substation; high-voltage shunt reactors disconnection; live-tank oil circuit breaker; reactive power 100 MVAr; switching overvoltage measurement; synchronize switching device; voltage 110 kV; voltage 200 kV; voltage 400 kV; Capacitance; Circuit breakers; Frequency; Inductors; Power measurement; Power system measurements; Power system reliability; Shunt (electrical); Switching circuits; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics, 2006 IEEE International Symposium on
  • Conference_Location
    Montreal, Que.
  • Print_ISBN
    1-4244-0496-7
  • Electronic_ISBN
    1-4244-0497-5
  • Type

    conf

  • DOI
    10.1109/ISIE.2006.295847
  • Filename
    4078522