Dielectric Strength and Statistical Property of Single and Triple-Break Vacuum Interrupters in Series
Author :
Min-fu, Liao ; Ji-yan, Zou ; Xiong-ying, Duan ; Xing-ming, Fan ; Hui, Sun
Author_Institution :
Dept. of Electr. & Electron. Eng., Dalian Univ. of Technol.
Abstract :
The maximum possible improvement factor of VCB with double or multiple breaks compared with one-break, which have the same equivalent gap length, is deduced. Simultaneously, from the research on the breakdown weak points in high voltage vacuum gaps, their turn out and distribution, a theoretic model was set up for describing the statistical property of multi-breaks VCB´s. This paper describes dielectric experiments on the commercial vacuum interrupter arrangements with single break or triple breaks in series. The experiments were carried out under lightning impulse voltage (LIV). It shows that the more numbers in series are, the higher the breakdown voltage improvement factor is. The statistical results show that the triple-break vacuum interrupters in series have the lower breakdown probability compared with the single-break one. It can be demonstrated in a preliminary study that the experimental results do confirm with the previous theoretical studies
Keywords :
electric strength; statistical analysis; vacuum interrupters; dielectric strength; lightning impulse voltage; single-break vacuum interrupters; statistical properties; triple-break vacuum interrupters; vacuum interrupter; Breakdown voltage; Dielectric breakdown; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Interrupters; Mechanical factors; Sun; Vacuum breakdown; Vacuum technology;
Conference_Titel :
Discharges and Electrical Insulation in Vacuum, 2006. ISDEIV '06. International Symposium on
Conference_Location :
Matsue
Print_ISBN :
1-4244-0191-7
Electronic_ISBN :
1093-2941
DOI :
10.1109/DEIV.2006.357256