• DocumentCode
    462912
  • Title

    Influence of Gap Distance on the Arc Modes Transition of Cup Type AMF Electrode

  • Author

    Shaoyong, Cheng ; Shixin, Xiu ; Jimei, Wang ; Xing, Li

  • Author_Institution
    Xi´´an Jiaotong Univ.
  • Volume
    1
  • fYear
    2006
  • fDate
    25-29 Sept. 2006
  • Firstpage
    384
  • Lastpage
    387
  • Abstract
    In this paper the influence of gap distance on arc modes transition of cup type AMF electrode is investigated by a CCD at different gap distance 10 mm to 20 mm. The arc keeps diffuse arc modes while the amplitude of arc current reaches 22.0 kA at gap distance 10 mm. With the gap distance increasing to 20 mm, the concentration of arc column near anode occurs while the amplitude of arc current is 14.0 kA. With the amplitude of arc current increasing, the duration time of the concentration of arc column near anode also increases at the same gap distance
  • Keywords
    CCD image sensors; circuit-breaking arcs; electrodes; vacuum arcs; vacuum circuit breakers; vacuum interrupters; 14.0 kA; 22.0 kA; CCD measurement; arc column concentration; arc current amplitude; arc modes transition; cup type AMF electrode; diffuse arc mode; gap distance; Anodes; Cathodes; Charge coupled devices; Circuit testing; Dielectrics and electrical insulation; Electrodes; Frequency; Plasma confinement; Vacuum arcs; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum, 2006. ISDEIV '06. International Symposium on
  • Conference_Location
    Matsue
  • ISSN
    1093-2941
  • Print_ISBN
    1-4244-0191-7
  • Electronic_ISBN
    1093-2941
  • Type

    conf

  • DOI
    10.1109/DEIV.2006.357312
  • Filename
    4194892