DocumentCode
467054
Title
UHF Characteristics of PD Monitoring in XLPE Cable Accessories
Author
Wang, Wei ; Zheng, Bin ; Li, Chengrong ; Zhang, Jifei ; Liu, Chong
Author_Institution
Beijing Key Laboratory of High Voltage & EMC; Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control, Ministry of Education, North China Electric Power University, Beijing, 102206, China. E-mail: wwang-bj@ieee.org
fYear
2007
fDate
8-13 July 2007
Firstpage
564
Lastpage
568
Abstract
In this paper, we experimented on the UHF characteristics of PD monitoring in XLPE cable accessories, such as four different types of PD signals[1]: cavity discharge signal, protrusion discharge signal, surface discharge signal and floating discharge signal. Also, the influence of mobile signals interference was discussed. The results showed that the mobile signal´s spectrum is broad when the phone signals are emited. The proper UHF measuring band was confirmed by simulation analysis, experiment in laboratory and test on site, it is between 1.2GHz to 1.6GHz. On-site PD detection had approved that this measuring band can suppress the interference effectively, and the detection sensitivity can reach to 48pC
Keywords
Background noise; Bandwidth; Frequency; Laboratories; Monitoring; Partial discharges; Power cables; Signal analysis; Testing; UHF measurements;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
Conference_Location
Winchester, UK
Print_ISBN
1-4244-0750-8
Electronic_ISBN
1-4244-0751-6
Type
conf
DOI
10.1109/ICSD.2007.4290876
Filename
4290876
Link To Document