• DocumentCode
    468473
  • Title

    The criterion on inter-turn short circuit fault diagnose of steam turbine generator rotor windings

  • Author

    Li Yong-Gang ; Sun Yi ; Wang Lin-li ; Li Hai-Bo

  • Author_Institution
    North China Electr. Power Univ., Beijing
  • fYear
    2007
  • fDate
    8-11 Oct. 2007
  • Firstpage
    1050
  • Lastpage
    1054
  • Abstract
    In this paper, the cause and its serious hazard of the inter-turn short circuit fault on turbine generator rotor windings are analyzed. Furthermore the electromagnetic characteristics and mechanical characteristics as well as the correlative variety of the electrical parameters induced after inter-turn short circuit fault on turbine generator rotor windings are analyzed. Based on the fault characteristics that the excitation current increased while the reactive power output decreased relatively when the inter-turn short circuit happens, a fault characteristic mathematical model of inter-turn short circuit is founded considering the saturated situation of steam generators.
  • Keywords
    fault diagnosis; mathematical analysis; reactive power; rotors; short-circuit currents; steam turbines; turbogenerators; electromagnetic characteristics; excitation current; interturn short circuit fault diagnosis; mathematical model; mechanical characteristics; reactive power; steam turbine generator rotor windings; Character generation; Circuit faults; Magnetic circuits; Magnetic flux; Magnetic forces; Mathematical model; Power generation; Reactive power; Rotors; Turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Machines and Systems, 2007. ICEMS. International Conference on
  • Conference_Location
    Seoul
  • Print_ISBN
    978-89-86510-07-2
  • Electronic_ISBN
    978-89-86510-07-2
  • Type

    conf

  • Filename