    Lightning surge into a substation at a back-flashover and review of lightning protective level through the FDTD simulation

  • Author

    Takami, J. ; Tsuboi, Toshihiro ; Yamamoto, Koji ; Okabe, Shigemitsu ; Baba, Yuya ; Ametani, Akihiro

  • Author_Institution
    Tokyo Electr. Power Co., Yokohama, Japan
  • Volume
    21
  • Issue
    3
  • fYear
    2014
  • fDate
    Jun-14
  • Firstpage
    1044
  • Lastpage
    1052
  • Abstract
    Higher accuracy in the lightning-surge analysis has been pursued; based on circuit analysis. However, the need to analyze phenomena where a plane wave propagation mode cannot be assumed is an outstanding issue. The finite-difference time-domain (FDTD) method is a dominant measure to solve such issue. This study evaluated surge waveforms intruding into a 500 kV air-insulated substation due to a back-flashover through FDTD simulation. The lightning surges were calculated with the inclined angle of the incoming line changed from 0 to 69 degrees and the voltage of the lightning surge intruding into the substation decreased with increasing incline angle of the incoming line. At the open end of the incoming line to the substation at the circuit breaker, the voltage was minimized and maximized when the span length was 20 m and 200 m respectively. This result differed in terms of characteristics from that obtained using the conventional circuit analysis model, whereby the voltage was minimized when the span length was 200 m. The lightning overvoltage at the circuit breaker terminal based on FDTD analysis was lower than that based on circuit analysis. Their relative ratio is 0.557 for a standard incoming line span length of 150 m, showing a 44 % reduction in FDTD analysis from the circuit analytical result. Since the current lightning impulse test voltage is evaluated based on this circuit analytical result, it was clarified that the lightning impulse test voltage level could be potentially reduced with consideration of the inclined conductors at the incoming line span, the vertical conductors of the tower and lightning path, and their mutual coupling with the transmission line.
  • Keywords
    circuit breakers; finite difference time-domain analysis; flashover; lightning protection; power transmission lines; substation insulation; substation protection; surge protection; FDTD simulation; air-insulated substation; back-flashover; circuit analysis model; circuit breaker terminal; current lightning impulse test voltage; finite-difference time-domain method; incline angle; inclined conductors; lightning impulse test voltage level; lightning overvoltage; lightning path; lightning protective level; lightning-surge analysis; line span; mutual coupling; plane wave propagation mode; surge waveforms; tower; transmission line; voltage 500 kV; Finite difference methods; Integrated circuit modeling; Lightning; Poles and towers; Substations; Surge protection; Surges; Transmission line; back-flashover; incoming line; lightning protection design; lightning surge; non-uniform line; substation;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2014.6832247
  • Filename
    6832247