• DocumentCode
    473182
  • Title

    Differential Protection Methodology for Arbitrary Three-Phase Power Transformers

  • Author

    Gajic, Z.

  • Author_Institution
    SA Products, ABB AB, Vasteras
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    44
  • Lastpage
    49
  • Abstract
    This paper describes how to provide universal, current based, differential protection for any three-phase power transformer, including phase-shifting transformers with variable phase angle shift and special converter transformers with nonstandard but fixed phase angle shift (e.g. 22.5deg). The use of standard transformer differential protection for such applications is considered impossible in the protective relaying standards and practices currently applied. This universal differential protection method only requires standalone CTs on all sides of the protected transformer. Thus, any buried current transformers within the tank of the protected power transformer are not required regardless transformer construction details and internal on-load tap-changer configurations.
  • Keywords
    power system protection; power transformer protection; arbitrary three phase power transformers; converter transformers; current transformers; differential protection methodology; on load tap changer configurations; phase angle shift; phase shifting transformers; Converters; Current transformers; Equations; Mathematical model; Power transformers; Relays; Windings;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4496958