• DocumentCode
    473191
  • Title

    Self-Adaptive Generator Protection Methods

  • Author

    Finney, Dale ; Kasztenny, Bogdan ; McClure, M. ; Brunello, Gustavo

  • Author_Institution
    Gen. Electr. Co., Markham, ON
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    98
  • Lastpage
    103
  • Abstract
    There are occasions in setting generator protection relays where the effective application of a protection function requires detailed measurement and analysis of operational data from the machine. This paper identifies two such functions: split phase protection and 3rd harmonic neutral under-voltage protection and discusses the particular application issues associated with each. A new algorithm is presented that can respond to the influencing system conditions and automatically adapt these functions accordingly. The resulting protection schemes are more sensitive, less likely to mis operate, and are easier to set than their conventional counterparts.
  • Keywords
    electric generators; power system harmonics; power system protection; relay protection; stators; 3rd harmonic neutral under-voltage protection; generator protection relays; inter-turn faults; protection function; self-adaptive generator protection methods; split phase protection; stator ground; Circuit faults; Generators; Harmonic analysis; Stator cores; Stator windings; Stators; Windings;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4496967