Title :
Secondary Arc Extinction and Detection Real and Simulated
Author :
Giesbrecht, J. ; Ouellette, D.S. ; Henville, C.F.
Author_Institution :
RTDS Technoligies Inc., Winnipeg, MB
Abstract :
Removal of a single line to ground fault by isolating only the faulted phase frequently leads to the creation of a secondary fault arc. Auto reclose protection schemes depend upon the absence of a secondary arc prior to reclosing. Consequently, there is great benefit from a technology to determine secondary arc extinction detection. The testing of SAED can be difficult and require the expense and complexity of staged system faults. A great deal of planning is necessary to do this however, and many fault scenarios cannot be fully studied. Accurate simulation of the phenomenon can alleviate many of these difficulties.
Keywords :
arcs (electric); power system faults; relay protection; auto reclose protection schemes; power system faults; relay response; secondary arc extinction; single line-to ground fault; testing; Atmospheric modeling; Capacitors; Circuit faults; Impedance; Mathematical model; Power transmission lines; Relays;
Conference_Titel :
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location :
Glasgow
Print_ISBN :
978-0-86341-902-7