DocumentCode :
473232
Title :
Accurate Location of Faults on Series-Compensated Lines with Use of Two-End Unsyncuronised Measurements
Author :
Saha, M.M. ; Izykowski, J. ; Rosolowski, E. ; Balcerek, P. ; Fulczyk, Marek
Author_Institution :
ABB AB, Stockholm
fYear :
2008
fDate :
17-20 March 2008
Firstpage :
338
Lastpage :
343
Abstract :
This paper presents accurate fault location algorithm for series compensated lines. Use of two-end current and voltage signals with a more general case of unsynchronised measurements is considered. Two ways of synchronisation of measurements are presented. The subroutines of the developed algorithm are formulated with use of the generalised fault loop model, leading to compact formulae. High accuracy of fault location is assured due to strict considering the distributed parameter line model. The distance to fault calculation is independent on the parameters of the compensating bank. Multi-criteria efficient procedure for selecting the valid subroutine is presented. The developed fault location algorithm has been thoroughly tested using signals taken from ATP-EMTP versatile simulations of faults on a series-compensated transmission line. The example of fault location is presented and discussed.
Keywords :
EMTP; power system faults; power transmission lines; ATP-EMTP; Electromagnetic Transients Program; distributed parameter line model; fault calculation; fault location algorithm; fault loop model; series compensated lines; series-compensated transmission line; two-end unsynchronised measurements; Algorithms; Current measurement; Equations; Fault location; Mathematical model; Synchronization; Voltage measurement;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location :
Glasgow
ISSN :
0537-9989
Print_ISBN :
978-0-86341-902-7
Type :
conf
Filename :
4497008
Link To Document :
بازگشت