  • Title

    Estimation of the Zero Sequence Voltage on the D-Side of a DY Transformer by Using One Voltage Transformer on the D-Side

  • Author

    Sulla, Francesco ; Samuelsson, Olof

  • Author_Institution
    Lund Univ., Lund
  • fYear
    2008
  • fDate
    17-20 March 2008
  • Firstpage
    517
  • Lastpage
    522
  • Abstract
    The usual practice to measure the zero sequence voltage on the D-side of a transformer is to use three voltage transformers (VT), each of them connected between each phase and earth on the primary side and broken-delta connected on the secondary side. In this paper a method is presented for the estimation of the zero sequence voltage on the D-side of a Dy transformer by the use of only one VT connected between one phase and earth on the D-side and three VTs and current transformers (CT) on the y-side. The method is first introduced theoretically. Results from simulations and laboratory tests are then presented. The method proved to be accurate with an observed maximum error around 7% of nominal phase-to-earth voltage during transformer energization and below 1% in all other cases.
  • Keywords
    current transformers; potential transformers; current transformers; nominal phase-to-earth voltage; transformer energization; voltage transformer; zero sequence voltage; zero sequence voltage estimation; Current transformers; Equations; Estimation; Impedance; Instrument transformers; Mathematical model; Voltage measurement;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
  • Conference_Location
    Glasgow
  • ISSN
    0537-9989
  • Print_ISBN
    978-0-86341-902-7
  • Type

    conf

  • Filename
    4497039