Title :
Effect of Statcom on Measured Impedance by Distance Relay in Double-Circuit Lines
Author :
Jamali, Shahram ; Kazemi, A. ; Shateri, H.
Author_Institution :
Centre of Excellence for Power Syst. Autom. & Oper., Iran Univ. of Sci. & Technol., Tehran
Abstract :
This paper presents the measured impedance at the relaying point in the presence of static synchronous compensator (STATCOM), a shunt connected flexible alternating current transmission system (FACTS) device, on a double circuit transmission line. The presence of STATCOM on a line has a great influence on the measured impedance by distance relays. The measured impedance by a distance relay itself depends on the power system structural conditions, pre-fault loading, and especially the earth fault resistance. In the presence of STATCOM, its structural and controlling parameters as well as its installation location affect the measured impedance. The measured impedance at relaying point is presented due to the concerning parameters.
Keywords :
power system relaying; power transmission lines; static VAr compensators; STATCOM; distance relay; double circuit transmission line; double-circuit lines; flexible alternating current transmission system device; static synchronous compensator; Automatic voltage control; Circuit faults; Electrical resistance measurement; Impedance; Impedance measurement; Power systems; Transmission line measurements;
Conference_Titel :
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location :
Glasgow
Print_ISBN :
978-0-86341-902-7