DocumentCode
473291
Title
Dynamic Line Rating Protection for Wind Farm Connections
Author
Yip, H.T. ; An, C.-H. ; Aten, M. ; Ferris, R.
Author_Institution
AREVA T&D UK Ltd., Stafford
fYear
2008
fDate
17-20 March 2008
Firstpage
693
Lastpage
697
Abstract
This paper describes how dynamic line rating is applied for load management and protection of a 132 kV line between Skegness and Boston (North East of England) thereby enabling a larger penetration of wind generation. The rating of the line is calculated dynamically from local weather measurements to co-ordinate allowed generation automatically. As a back-up system, in case for some reason the wind farm power output is not reduced on command by the control system, it is proposed that a relay will initiate tripping of wind generators.
Keywords
power generation protection; wind power plants; cload management; cload protection; clocal weather measurements; cwind generation; dynamic line rating protection; voltage 132 kV; wind farm connections; Conductors; Equations; Mathematical model; Meteorology; Temperature measurement; Wind; Wind speed;
fLanguage
English
Publisher
iet
Conference_Titel
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location
Glasgow
ISSN
0537-9989
Print_ISBN
978-0-86341-902-7
Type
conf
Filename
4497068
Link To Document