DocumentCode :
473296
Title :
Practical Experinences with Faulty Feeder Indentification Using Transient Signals
Author :
Xue Yongduan ; Xu Bingyin ; Ma Shicong ; Wang Tao
Author_Institution :
Kehui Electr. Ltd., Zibo
fYear :
2008
fDate :
17-20 March 2008
Firstpage :
720
Lastpage :
723
Abstract :
The faulty feeder identification method for the non-effectively earthed network using transient signals is introduced. Practical field experiences with the method are presented. The transient method is proved effective in identifying the feeder with the metal and low resistance fault, while further investigation is needed to improve its high resistance performances. Analysis to the field recordings revealed some of the permanent faults have foreboding temporary faults. The transient method offers the possibility of identifying feeders with the incipient faults, which provides valuable condition monitoring information.
Keywords :
earthing; power distribution faults; power distribution protection; power system transients; condition monitoring information; faulty feeder identification; noneffective earthed distribution network; transient signal; Capacitance; Circuit faults; Fault diagnosis; Metals; Resistance; Substations; Transient analysis;
fLanguage :
English
Publisher :
iet
Conference_Titel :
Developments in Power System Protection, 2008. DPSP 2008. IET 9th International Conference on
Conference_Location :
Glasgow
ISSN :
0537-9989
Print_ISBN :
978-0-86341-902-7
Type :
conf
Filename :
4497073
Link To Document :
بازگشت