• DocumentCode
    481869
  • Title

    Stability analysis of doubly-fed induction wind generator operating at low power factor mode

  • Author

    Zheng, Yanwen ; Li, Yongdong ; Chai, Jianyun

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing
  • fYear
    2008
  • fDate
    10-13 Nov. 2008
  • Firstpage
    2241
  • Lastpage
    2246
  • Abstract
    This paper presents an analysis of the reactive power capability (RPC) of doubly-fed induction generators (DFIG) system from the stability point of view. The stator flux orientated control (SFOC) is adopted in the DFIG system and the dynamics of rotor current is considered. The analytic stability of SFOC DFIG system has been deduced and verified on a 30 kW DFIG system using a back-to-back converter. It is shown that the stability and damping of the SFOC DFIG system depends on the reactive component of the rotor current and band width of rotor current loop.
  • Keywords
    asynchronous generators; power convertors; stability; back-to-back converter; doubly-fed induction wind generator; power 30 kW; power factor mode; reactive power capability; rotor current; stability analysis; stator flux orientated control; Control systems; Damping; Induction generators; Power generation; Reactive power; Rotors; Stability analysis; Stators; Wind energy generation; Wind power generation; DFIG; Reactive capacity; Stability; Wind energy;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Industrial Electronics, 2008. IECON 2008. 34th Annual Conference of IEEE
  • Conference_Location
    Orlando, FL
  • ISSN
    1553-572X
  • Print_ISBN
    978-1-4244-1767-4
  • Electronic_ISBN
    1553-572X
  • Type

    conf

  • DOI
    10.1109/IECON.2008.4758305
  • Filename